EV charger with built-in BESS
120 kWh · 30 kW grid input · 60 kW shared output
One enclosure combines a 120 kWh LFP battery, a 30 kW bidirectional grid module and reversible DC-DC modules. The battery charges slowly from the grid and delivers fast DC charging to two CCS-2 guns, while AC Type 2, a 3.3 kW socket and a light-EV Type 6 / 7 output run from the same system. On grid failure, enabled outputs keep running on battery.
How the energy moves.
System power flow · 120 kWh BESS | 30 kW grid charging | 60 kW shared output
Scroll the diagram sideways →
Conceptual architecture. Case 1 and Case 2 use the same DC modules in mutually exclusive modes. The 60 kW cap includes AC, CCS-2 and light-EV outputs. Pack topology is illustrative; converter voltage range, usable-energy window and final topology are confirmed at order.
Normal operation
- Grid → 30 kW AC-DC module → battery, at up to 30 kW.
- Battery → DC-DC modules → CCS-2: one EV at up to 60 kW, or two at 30 kW each.
- EMS allocates the 60 kW shared cap across CCS-2, AC and light-EV outputs.
Grid failure
- Grid is isolated automatically.
- Enabled outputs continue on battery-backed supply.
- On grid return, battery charging resumes under EMS limits.
External DC recharge
- The same reversible DC-DC modules accept up to 60 kW from a compatible external DC charger.
- The BESS acts as the charging client through an interlocked CCS-2 inlet.
- Roughly 2 h for 120 kWh at 60 kW on an ideal energy basis.
Technical specification.
Power conversion & outputs
- Grid / AC conversion1 × 30 kW bidirectional AC-DC module
- CCS-2 DC charging2 × 30 kW DC-DC · 60 kW combined
- CCS-2 allocation1 EV up to 60 kW · 2 EVs at 30 kW each
- AC outputs1 × 22 kW Type 2 · 1 × 3.3 kW socket
- Light-EV output3 kW DC-DC · Type 6 / 7 · 40–58 V, 50 A
- Shared output cap60 kW combined, EMS-managed
- Vehicle protocolsDIN 70121 · ISO 15118-2
Battery
- CellLFP · 3.2 V · 314 Ah
- Pack16S · 51.2 V nominal · 16.08 kWh
- Illustrative bank8 packs in series · 409.6 V · 128.6 kWh nominal
- Backup requirement120 kWh
- BMS16S per pack · active (2 A) + passive balancing
Control, metering & protection
- EMSPower allocation · SOC limits · operating modes
- Charging controllerVehicle comms · converter commands · interlocks
- MeteringGrid, battery and per-output energy meters
- ProtectionAC/DC contactors · breakers / fuses · DC pre-charge & isolation
- MonitoringOnline status, SOC, remote start / stop
Design-basis values from a TOBOR project offer. *Cycle life depends on cell OEM specification, depth of discharge, temperature, C-rate and end-of-life criterion. Final ratings, certifications and performance guarantees follow the approved project-specific design.
- Sites where the grid connection is too small for a 60 kW DC charger
- Fleet and cab hubs mixing cars, 3W and 2W
- CPO locations that need charging to continue through outages
- Interim sites waiting for a grid upgrade