Utility-scale · 2 MW – 10 MW

CTX-5000CTX 2.5 MW · 2.5 MW / 5.06 MWh · ~2 h

20 ft container · 20 racks · 5,040 LFP cells · Energy arbitrage · peak shaving · frequency response · renewable firming

2.5 MW / 5.06 MWh in a single 20 ft high-cube container. Twenty 806 V LFP racks, each with its own 125 kW PCS module, liquid cooling with N+1 chillers and a dedicated 2.75 MVA 0.4/33 kV unit transformer. Stack containers for 5, 7.5 or 10 MW.

TOBOR CTX-5000 — 20 ft container · 20 racks · 5,040 LFP cellsCTX series · representative image
Power
2.5 MW
Energy
5.06 MWh
Usable @ 90% DoD
4,558 kWh
Cycles
8,000
Specification · CTX-5000

Full technical sheet.

Electrical output

  • Continuous max power2,500 kW
  • Output voltage400 V AC (-20 / +15%)
  • Rated output current3,608 A
  • Phase / frequency3-phase 4-wire · 50 Hz (47–52 Hz)
  • Power conversion20 × 125 kW modules (one per rack)
  • PCS efficiency98.5% peak
  • MV interface2.75 MVA · 0.4 / 33 kV unit transformer

Energy storage

  • Nameplate capacity5,064 kWh
  • CellLiFePO4 · 3.2 V · 314 Ah
  • Pack / rack14S1P 44.8 V · 252S1P 806.4 V
  • Rack energy253.2 kWh
  • Racks per container20 (5,040 cells)
  • DC operating window730.8–894.6 V
  • Design cycle life8,000 cycles

Environment & ownership

  • Form factor20 ft ISO high-cube
  • Dimensions6,058 × 2,438 × 2,896 mm
  • Weight~40 t
  • CoolingLiquid · N+1 chillers
  • Operating temp-30 °C → +55 °C
  • Ingress / corrosionIP55 · C4 (C5-M option)
  • OriginMade in India · Gurugram

Control & interface

  • Battery managementIn-house TOBOR BMS
  • Energy managementIn-house TOBOR EMS
  • CommunicationsModbus TCP · CAN · RS485
  • Fire safetyProject-specific verification

Catalogue values. *Cycle capability depends on depth of discharge, C-rate, temperature and end-of-life criterion. Peak PM efficiency is not whole-system round-trip efficiency. Usable energy and runtime depend on permitted DoD, conversion losses and auxiliaries. Final ratings and compliance follow the approved project-specific offer.

Compatible applications

Where this size fits.

Energy arbitrage

Charge in low-price blocks and discharge into evening peaks. 8,000-cycle LFP and liquid cooling built for daily cycling.

Frequency response & ancillary services

Sub-100 ms full reversal and < 200 ms 0–100% ramp at block level, with IEC 61850 plant control.

Renewable firming

Co-locate with solar or wind to shape output, firm capacity and reduce curtailment at the point of interconnection.

Black start & islanding

Block-level black-start capability with DG-backed auxiliaries, subject to the approved single-line design.

Ready to size your project?

Share your interval load data, tariff and grid limits. Our engineers return a kW / kWh sizing, dispatch logic and a techno-commercial offer.

Request quote

Questions and answers

What is the CTX-5000?
2.5 MW / 5.06 MWh in a single 20 ft high-cube container. Twenty 806 V LFP racks, each with its own 125 kW PCS module, liquid cooling with N+1 chillers and a dedicated 2.75 MVA 0.4/33 kV unit transformer. Stack containers for 5, 7.5 or 10 MW.
What loads does the CTX-5000 support?
Sized for Energy arbitrage · peak shaving · frequency response · renewable firming. Rated output 2.5 MW, with 5.06 MWh of nameplate LFP energy. Energy arbitrage, frequency response, renewable firming and black start at utility scale.
Where is the CTX-5000 manufactured?
Designed and manufactured at the TOBOR facility in Gurugram, Haryana, India. BMS, EMS, power conversion and firmware are engineered in-house; LFP cells are integrated into TOBOR-engineered packs and racks.