Utility-scale · 2 MW – 10 MW
CTX-5000CTX 2.5 MW · 2.5 MW / 5.06 MWh · ~2 h
20 ft container · 20 racks · 5,040 LFP cells · Energy arbitrage · peak shaving · frequency response · renewable firming
2.5 MW / 5.06 MWh in a single 20 ft high-cube container. Twenty 806 V LFP racks, each with its own 125 kW PCS module, liquid cooling with N+1 chillers and a dedicated 2.75 MVA 0.4/33 kV unit transformer. Stack containers for 5, 7.5 or 10 MW.
Full technical sheet.
Electrical output
- Continuous max power2,500 kW
- Output voltage400 V AC (-20 / +15%)
- Rated output current3,608 A
- Phase / frequency3-phase 4-wire · 50 Hz (47–52 Hz)
- Power conversion20 × 125 kW modules (one per rack)
- PCS efficiency98.5% peak
- MV interface2.75 MVA · 0.4 / 33 kV unit transformer
Energy storage
- Nameplate capacity5,064 kWh
- CellLiFePO4 · 3.2 V · 314 Ah
- Pack / rack14S1P 44.8 V · 252S1P 806.4 V
- Rack energy253.2 kWh
- Racks per container20 (5,040 cells)
- DC operating window730.8–894.6 V
- Design cycle life8,000 cycles
Environment & ownership
- Form factor20 ft ISO high-cube
- Dimensions6,058 × 2,438 × 2,896 mm
- Weight~40 t
- CoolingLiquid · N+1 chillers
- Operating temp-30 °C → +55 °C
- Ingress / corrosionIP55 · C4 (C5-M option)
- OriginMade in India · Gurugram
Control & interface
- Battery managementIn-house TOBOR BMS
- Energy managementIn-house TOBOR EMS
- CommunicationsModbus TCP · CAN · RS485
- Fire safetyProject-specific verification
Catalogue values. *Cycle capability depends on depth of discharge, C-rate, temperature and end-of-life criterion. Peak PM efficiency is not whole-system round-trip efficiency. Usable energy and runtime depend on permitted DoD, conversion losses and auxiliaries. Final ratings and compliance follow the approved project-specific offer.
Where this size fits.
Energy arbitrage
Charge in low-price blocks and discharge into evening peaks. 8,000-cycle LFP and liquid cooling built for daily cycling.
Frequency response & ancillary services
Sub-100 ms full reversal and < 200 ms 0–100% ramp at block level, with IEC 61850 plant control.
Renewable firming
Co-locate with solar or wind to shape output, firm capacity and reduce curtailment at the point of interconnection.
Black start & islanding
Block-level black-start capability with DG-backed auxiliaries, subject to the approved single-line design.